Product Description
The Assured Automation MAG series are volumetric magnetic induction flow meters that measure flow rate and totals at rates up to 160 gpm, and also measure temperature. The rugged meter body includes electronics, display, user interface, and output signal generation in one compact unit. In addition to being more compact it is also less expensive than comparable meters and sensors.
Output Signals: Analog, binary, pulse and frequency outputs offer various options to process the measured data. The meter is designed for the brewing, HVAC, machine tool, solar, and water industries. It is used with conductive liquids [conductivity: ≥ EC 0.02 (12.8 ppm TDS, 20 µS/cm) / viscosity: < 0.1085 in²/s at 104 °F].
Output Signal Options
Digital:
These units have 2 outputs that can be configured in the field to provide various switching options, frequency signals, or pulse output. Output 2 does have analog signal options. All switching outputs can be set to N.O. or N.C.
Output 1 Options:
• Switching output empty pipe detection
• Switching output Volumetric flow rate monitoring
• Frequency output flow rate
• Pulse output for totalizing
• Signal output preset counter
Output 2 Options:
• Switching output empty pipe detection
• Switching output based on flow rate
• Switching output based on temperature
• Analog output of flow rate (4-20mA or 0-10VDC)
• Analog output of temperature (4-20mA or 0-10VDC)
• Use as an input for TOTALIZER reset
Medium | Conductive |
Not Conductive |
Acetic acid | X | |
Acetone | X | |
Alcohol |
X | |
Beer |
X | |
Blood |
X | |
Body lotion |
X | |
Cleaning agents |
X | |
Coffee extract | X | |
Corn syrup |
X | |
Fruit juice |
X | |
Glycol / water mixture |
X | |
Hydrochloric acid |
X | |
Hydrogen peroxide |
X | |
Latex paint |
X | |
Nitric acid |
X | |
Oils |
X | |
Potassium hydroxide |
X | |
Salt water |
X | |
Shampoo | X | |
Sugar (pure) |
X | |
Sugar (diluted with water) |
X | |
Sulfuric acid (dilute) |
X | |
Water (deionized) |
X | |
Water |
X | |
Water-based Coolant | X |
Custom Programming at Factory
If you want your meter to come pre-programmed to your specifications at the factory, simply check the box when ordering. We will contact you for complete specifications once the order is received.
This includes:
- What gets displayed
Flow Rate, Flow Total, or Temperature - What each output does
Switching, Pulse, Frequency, Analog, Reset, or I/O Link - The details of each output
Scaling start and end points, switching type, switching points, pulse value, dampening, etc.